8 Digital ac/dc (24V) Input Module

Publication 1771-IN052B-EN-P - April 2006

Connect Wiring

Connect your I/O devices to the field wiring arm, cat. no. 1771-WH, shipped with the
module.

You can use an ac (24V) output module (cat. no. 1771-OND/B) to directly drive terminals on
an ac/dc (24V) input module (cat. no. 1771-IND/C) as shown below.

ATTENTION

Remove power from the 1771 I/O chassis backplane before you install this module.
Failure to remove power from the backplane could cause:

• module damage or degradation of performance.
• injury or equipment damage due to possible unexpected operation.

(Actual wiring runs in this direction.)

L1

ac/dc High

ac/dc Low

L2

Terminal A must be connected to
L1 to balance the line in an
ungrounded application.

Input 00
Input 01

Input 02

Input 03
Input 04

Input 05

Input 06

Input 07
Input 10

Input 11
Input 12

Input 13
Input 14

Input 15
Input 16
Input 17

A

B

C

D

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

E

10426-I

T erminal B

T erminal A

T erminal C
T erminal D

T erminal E

1. Connect one terminal of your 2-wire input devices to

terminals 00 through 17.

2. Connect terminal E to the L2 (low) ac return.

Terminals A through D are not used. (Note: In
ungrounded applications, connect terminal A to L1 to
balance the line.) Connect the L1 (high) ac line to the
other terminal of your input devices. Use maximum
2.5 mm

2

(14 AWG) stranded copper wire to minimize

the voltage over long cable distances.