Specifications – Rockwell Automation 1792D-16VT0LP INSTL INSTR ARMORBLOCK INPUT User Manual
Page 7

7
ArmorBlock LP2 16 Sourcing Input Module
Publication 1792D-5.28 - January 1999
Specifications
Network Status Indicator
Indication
Status
None
Not On-line
Green
Blinking
Solid
On-line/No Connections
On-line/Connected
Red
Blink
Solid
Connection Timed Out
Failed Communication: A duplicate
node address exists or the module is at
the wrong baud rate.
I/O Status Indicators
Function
Module Status Indicator
Point Indicator
Condition
Inputs
Green
Green
None
Yellow
No valid input
Valid input
16 Input Module - Cat. No. 1792D-16VT0LP
Sourcing Input Specifications
Max
Min
Inputs per block
16 - 3 wire or dry contact NPN devices or 8 - 4 wire
NPN devices
Sensor Source Current (per input)
50mA per point
Off-Wire Sense Current
0.5mA
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5V dc
Off-state Current
1.5mA
General Specifications
Indicators
Network Status - red/green
Module Status - red/green
Point LED - yellow
Communication Rate
• 125Kbps @ 500 meters(1600 feet) for thick
cable, flat media length 375 meters
• 250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters