GuardPLC Digital Input/Output Module 15

Rockwell Automation Publication 1753-IN003C-EN-P - June 2010

Digital Outputs

Number of outputs

8 (not electrically isolated)

Output voltage range

L+ minus 2V

Output current

channels 1…3 and 5…7: 0.5 A @ 60 °C (140 °F)
channels 4 and 8: 1 A @60 °C (140 °F), 2 A @ 50 °C (122 °F)

Surge current per channel

1 A for 10 ms @ 1Hz (channels 1…3 and 5…7)
4 A for 10 ms @ 1Hz (channels 4 and 8)

Current load, min

2 mA per channel

Internal voltage drop

2V max @ 2 A

Leakage current (with 0
signal)

1 mA max @ 2V

Total output current

7 A max with exceeding shut down of all outputs with cyclic reconnecting

Response overload

Shut down of the concerned output with cyclic reconnecting

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Technical Specifications – 1753-IB20XOB8 Module