Saving parameters – Rockwell Automation 1746-QS,D17466.19 SYNCHRONIZED AXES MODULE User Manual
Page 26

4–10
Publication 1746-6.19 March 1998
6. Back down the value below no motion. Write down this valve.
7. Repeat steps 1-6 with negative values for opposite direction.
8. Determine
DEAD BAND ELIMINATOR
value. It is the larger of the
values from step 6, regardless of sign (
").
9. Enter the value of the
DEAD BAND ELIMINATOR
in the number
field in the Parameter section of the main screen.
10.Transfer the parameter to the module using the “P” Command.
At any time during tuning, you can save configuration parameters:
•
For PC backup, save the file of configuration parameters from the
Hydraulic Configurator with the “Save-as” function.
•
Store them in integer (N) files of the SLC processor to insure that
the ladder program matches the configuration parameters, issue a
ladder logic command to copy the M1 file of configuration
parameters from the module into SLC processor integer (N) files.
For ladder logic examples, refer to chapter 5.
Saving Parameters