AC/DC (220V) Input Module Cat. No. 1771-IMD Series B

Publication 1771Ć5.27

The front panel of your module contains one green, module active
LED, and 16 red status LED indicators. The 1771-IMD performs
diagnostics in a handshaking mode when first powered up. Upon
successful completion of the diagnostics, the green module active
indicator lights. It turns off if a fault occurs in the data paths or the
opto-isolators.

ACTIVE

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Module Active Indicator (green)

00 to 17 Status Indicators (red)

10552ĆI

If a module fault occurs, the module resets its inputs or sets them to
last state, depending on the fault mode selection. The module active
indicator must be on to properly interpret the red status indicators.

The red status indicators are provided for system logic side
indication of individual inputs. When a red indicator lights, voltage
is present on the terminal. The module transfers this information to
the backplane for the processor to read. See ”Troubleshooting” for a
description, probable cause, and recommended action to take for
common faults based on indicator responses.

Use this table to help you interpret the 1771-IMD status indicators
and to troubleshoot module and system faults.

Indicator Status (color)

Description of Fault or System Status

Action to Take

Module active ON (green)

Normal Indication

None

Module active ON (green) and

Input status ON (red)

Check for voltage on terminal

If none, replace module

Module active ON (green) and

Input status OFF

Input devices not functioning properly or faulty

input circuitry on module

1. Check input devices

2. If input devices are OK, replace module

No voltage on terminal

None

Module active OFF

Module is not powered or fault in optoĆisolators

and/or data paths; module resets inputs or goes to

last state

1. Check chassis power supply and module

input power

2. If power supplies are OK, replace module

Module active OFF and

Input status ON (red) or OFF

Not valid unless module active indicator is on;

when active is off, indicators do not represent

processor status

1. Check chassis power supply and module

input power

2. If power supplies are OK, replace module

Interpreting the Status

Indicators

Troubleshooting