Specifications – Rockwell Automation 1794-OB8_OB8EP_OB16_OB16P_OB32P Flex I/O Digital DC Sourcing Output Modules Installation Instructions User Manual

Page 5

Advertising
background image

5

Publication 1794-IN094B-EN-P - April 2004

Programming the 1794-OB8EP and -OB8EPK

If your program automatically checks for fault bits, bits 8

thru 15 of read word 1 must be masked. This is a sample

program for a module at rack address 1, group 0. Add

similiar rungs to your program.

Resetting a Fault on the 1794-OB8EP or -OB8EPK

Faults can be reset 3 ways: press the fault reset button on
the front of the module; or toggle the output reset bit
(write word 1, bit 08); or cycle backplane power.

Using the Reset Button on the 1794-OB8EP or
-OB8EPK

When you press the reset button, the fault indicator for
the faulted output turns off for about 1.2s. After the
delay, the faulted output attempts to turn on. If the
external condition causing the fault is corrected, the
output will remain on, the fault indicator is off, and the
status indicator is on.

Configuring Your 1794-OB8, -OB16, -OB16P and -OB32P Output
Module

You configure your output module by setting bits in the
configuration word (word 3).

Specifications

Surge Current for the 1794-OB8EP and -OB8EPK

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

Not used

Write

O
15

O
14

O
13

O
12

O
11

O
10

O
9

O
8

O
7

O
6

O
5

O
4

O
3

O
2

O
1

O
0

Write
1794-OB32P
only

O
31

O
30

O
29

O
28

O
27

O
26

O
25

O
24

O
23

O
22

O
21

O
20

O
19

O
18

O
17

O
16

Where O = Output - O0 corresponds to output 0, O1 corresponds to output 1, etc.
1794-OB8 uses outputs 0-7; 1794-OB16 and -OB16P use outputs 0-15; 1794-OB32P uses outputs 0-31.

MVM

CMP

Source
Mask
Destination

MASKED MOVE

Compare
Expression

N9: < > 0

I:010
FF00
N9:0

O:000

( Out )

This rung turns on output if a fault occurs.

This rung masked bits 8 thru 15.

Specifications - 24V dc 8 Output Module, Cat. No. 1794-OB8

Number of Outputs

8, nonisolated, sourcing

Module Location

Cat. No. 1794-TB2, -TB3, -TB3S

On-state Current

1.0mA minimum per channel
500mA maximum per channel

Output Current Rating

4.0A (8 outputs @ 0.5A)

Surge Current

2A for 50ms, repeatable every 2s

Off-state Leakage

0.5mA maximum

On-state Voltage Drop

0.5V dc maximum

Isolation Voltage

Tested at 850V dc for 1s between user and system
No isolation between individual channels

Output Signal Delay

Off to On - 0.5ms maximum
On to Off - 1.0ms maximum

Flexbus Current

60mA

Power Dissipation

3.3W maximum @ 31.2V dc

Thermal Dissipation

Maximum 11.2 BTU/hr @ 31.2V dc

Indicators (field side
indication, logic driven)

8 yellow status indicators

Fusing

Module outputs are not fused. Fusing is recommended. If fusing is
desired, you must provide external fusing. Use SAN-O MQ4-800mA fuses

Specifications - 24V dc 8 Output Module, Cat. No. 1794-OB8EP
and -OB8EPK

Number of Outputs

8 (1 group of 8), nonisolated, sourcing

Module Location

Cat. No. 1794-TB2, -TB3, -TB3S, -TBN

On-state Current

1.0mA minimum per channel
2A maximum per channel

Output Current Rating

Maximum 2A per output, 10A maximum per module (e.g. 8 outputs @
1.25A, 5 outputs @ 2A, or similar combinations totaling 10A or less)

Surge Current

4A for 10ms, repeatable every 3s (see chart)

Off-state Leakage

0.5mA maximum

On-state Voltage Drop

0.2V dc maximum

Isolation Voltage

Tested at 850V dc for 1s between user and system
No isolation between individual channels

Output Signal Delay

Off to On - 0.5ms maximum
On to Off - 1.0ms maximum

Flexbus Current

73mA

Power Dissipation

5.5W maximum @ 31.2V dc

Thermal Dissipation

Maximum 18.8 BTU/hr @ 31.2V dc

Indicators (field side
indication, logic driven)

8 yellow status indicators
8 red fault indicators

Fusing

Outputs are electronically fused

0

10

20

30

40

50

0

5

10

15

20

Output Minimum Surge Current

Time - ms

Surge Current - A