Specifications – Rockwell Automation 1786-RPA/B ControlNet Modular Repeater Adapter Installation Instructions User Manual

Page 19

Advertising
background image

ControlNet Modular Repeater Adapter 19

Rockwell Automation Publication 1786-IN013F-EN-P - April 2011

Specifications

Technical Specifications - 1786-RPA/B

Attribute

1786-RPA/B

Power consumption, max

16.8 W

Power dissipation, max

8.8 W

Input voltage rating, max

700 mA @ 24V DC, Class 2/SELV

(1)

(1)

For applications within the U.S., use a power supply that is appropriately certified as Class 2 per the
definition in the National Electrical Code, ANSI/NFPA 70, Article 725. For applications outside the
U.S., use a power supply with safety extra low voltage (SELV) or protected extra low voltage (PELV)
output. A power supply with SELV or PELV output is built with appropriate isolation to withstand single
fault conditions. The output cannot exceed 30V rms, 42.4V peak, or 60V DC under fault conditions.

Input voltage range

18…36V DC

Backplane output current, max

1.6A @ 5V DC

Minimum enclosure size (HxWxD), approx

304.8 x 196.8 x 101.6 mm
(12 x 7.75 x 4 in.)

Mounting orientation

Any mounting orientation

Isolation voltage

50V (continuous), Basic insulation type,
Power to system
Type tested at 710V DC for 60 s

Wire size

0.21…3.3 mm

2

(24...12 AWG) solid or

stranded copper wire rated at 75 °C

(167 °F ), or greater, 1.2 mm (3/64 in.)
insulation max for power connections

Wiring category

2 - on power ports
2 - on communication ports

(2)

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Enclosure type rating

None (open-style)

North American temp code

T5

IEC temp code

T4

Advertising