North american hazardous location approval, Prevent electrostatic discharge – Rockwell Automation 1769-ECR Compact I/O End Caps/Terminator User Manual
Page 4
 
4 Compact I/O End Caps/Terminators
Publication 1769-IN015C-EN-P - October 2008
Prevent Electrostatic Discharge
North American Hazardous Location Approval
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage 
and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
The following information applies when operating 
this equipment in hazardous locations.
Informations sur l’utilisation de cet équipement en 
environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in 
Class I Division 2 Groups A, B, C, D, Hazardous Locations and 
nonhazardous locations only. Each product is supplied with 
markings on the rating nameplate indicating the hazardous 
location temperature code. When combining products within a 
system, the most adverse temperature code (lowest "T" number) 
may be used to help determine the overall temperature code of 
the system. Combinations of equipment in your system are subject 
to investigation by the local Authority Having Jurisdiction at the 
time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent 
qu'à une utilisation en environnements de Classe I Division 2 
Groupes A, B, C, D dangereux et non dangereux. Chaque produit 
est livré avec des marquages sur sa plaque d'identification qui 
indiquent le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés dans un 
système, le code de température le plus défavorable (code de 
température le plus faible) peut être utilisé pour déterminer le 
code de température global du système. Les combinaisons 
d'équipements dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de l'installation.
WARNING
EXPLOSION HAZARD -
• Do not disconnect equipment
unless power has been removed 
or the area is known to be 
nonhazardous. Do not disconnect 
equipment unless power has 
been removed or the area is 
known to be nonhazardous. 
• Do not disconnect connections to
this equipment unless power has 
been removed or the area is 
known to be nonhazardous. 
Secure any external connections 
that mate to this equipment by 
using screws, sliding latches, 
threaded connectors, or other 
means provided with this product.
• Substitution of components may
impair suitability for Class I, 
Division 2.
• If this product contains batteries,
they must only be changed in an 
area known to be nonhazardous.
AVERTISSEMENT
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer
que l'environnement est classé 
non dangereux avant de 
débrancher l'équipement.
• Couper le courant ou s'assurer
que l'environnement est classé 
non dangereux avant de 
débrancher les connecteurs. Fixer 
tous les connecteurs externes 
reliés à cet équipement à l'aide 
de vis, loquets coulissants, 
connecteurs filetés ou autres 
moyens fournis avec ce produit.
• La substitution de composants
peut rendre cet équipement 
inadapté à une utilisation en 
environnement de Classe I, 
Division 2.
• S'assurer que l'environnement est
classé non dangereux avant de 
changer les piles.