ArmorBlock-LP 16 Input Module

8

Publication 1792-5.6 – September 1997

Network Status Indicator NS

Indication

Status

Flashing Green

On-line, not connected

Solid Green

Link OK, on-line connected

Flashing Red

At least 1 I/O connection is in the timed-out state

Solid Red

Incorrect baud rate, or a duplicate Mac ID exists

Module Status Indicator MS

Indication

Status

OFF

No power, or no network access

Flashing Green/OFF

On-line but not connected

Solid Green

On-line, link okay, connected

Flashing Red

Recoverable fault

Solid Red

Critical failure

Sensor Short Circuit Indicator OVL

Indication

Status

OFF

Sensor source voltage operating correctly

Solid Red

1 or more Sensor source voltage shorts

Input I/O Status Indicators A and B

Indication

Status

OFF

No valid input signal present

Yellow

Valid input signal present

Module and Sensor Power Supply Status Indicators U

S

and U

L

Indication

Status

OFF

Power supply is not functioning correctly

Green

Power Supply is operating