Input specifications – Rockwell Automation 1769-IA8I Compact Individually Isolated 120V ac Input Module User Manual

Page 13

Advertising
background image

Compact™ Individually Isolated 120V ac Input Module 13

Publication 1769-IN012B-EN-P

Input Specifications

Specification

1769-IA8I

Voltage Category

100/120V ac

Operating Voltage Range

79V ac to 132V ac at 47 Hz to 63 Hz

Number of Inputs

8

Isolated Groups

8 individually isolated inputs

Bus Current Draw (max.)

90 mA at 5V dc (0.45W)

Heat Dissipation

1.81 Total Watts (The Watts per point, plus the minimum Watts,
with all points energized.)

Signal Delay (max.)

On Delay: 20.0 ms

Off Delay: 20.0 ms

Off-State Voltage (max.)

20V ac

Off-State Current (max.)

2.5 mA

On-State Voltage (min.)

79V ac

On-State Current

5.0 mA at 79V ac (min.)

12 mA at 120V ac (nominal)

Inrush Current (max.)

1

1. A current limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac

input circuit will be affected. If a 6.8K

(2.5W minimum) resistor is placed in series with the input, the inrush

current is reduced to 35 mA. In this configuration the minimum on-state voltage increases to 92V ac.

Before adding the resistor in a hazardous environment, be sure to consider the operating temperature of the
resistor and the temperature limits of the environment. The operating temperature of the resistor must remain
below the temperature limit of the environment.

250 mA

Nominal Impedance

12K

at 50 Hz

10K

at 60 Hz

IEC Input Compatibility

Type 1+

Power Supply Distance Rating

8 (The module may not be more than 8 modules away from the
power supply or controller.)

Input Point to Bus Isolation

Verified by one of the following dielectric tests: 1517V ac for 1
sec. or 2145V dc for 1 sec.

132V ac working voltage (IEC Class 2 reinforced insulation)

Isolated Groups

8: Each point is individually isolated from the other.

Group to Group Isolation

Verified by one of the following dielectric tests: 1517V ac for 1
sec. or 2145V dc for 1 sec.

132V ac working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

81

Advertising