FLEX™ I/O Isolated Input/Output Analog Module 5

Publication 1794-IN039F-EN-P - November 2011

Isolation voltage

120V (continuous), Basic Insulation Type, channel to channel, channel to user,
channel to system, and user power to system when used with 1794-TB2,
1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS.

250V (continuous), Basic Insulation Type, channel to channel, channel to user,
channel to system, and user power to system when used with 1794-TBN.

Type tested at 1000V AC for 60 s.

Indicators

1 red/green power/status indicator

Keyswitch position

5

Dimensions, with module
installed in base; HxWxD

94.0 x 94.0 x 66.0 mm

(3.7 x 3.7 x 2.6 in.)

Calibration

Factory-calibrated for 150 Hz, 300 Hz, and 600 Hz. Can be recalibrated when
necessary.

Conductor category

(1)

2 – on signal ports

2 – on power ports

Conductor wire size

Determined by installed terminal base

Wire type

Shielded on signal ports

North American temp code

T4A

IEC temp code

T4

(1)

Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Input Specifications

Attribute

Value

Number of inputs

2 isolated

Resolution

Voltage

Current

16 bits – unipolar; 15 bits plus sign – bipolar

0.156 mV/cnt unipolar; 0.313 mV/cnt bipolar

0.320

A/cnt unipolar; 0.640 A/cnt bipolar

Data format

2’s complement

2’s complement %

Binary

Offset binary

Conversion type

Sigma Delta

Update rate

2.5/5.0/7.5 ms all channels (see

Update Rate for Real Time Sample Interval = 0

table)

Input current terminal

4…20 mA (user configurable)

0…20 mA (user configurable)

±20 mA (user configurable)

Input voltage terminal

±10V (user configurable)

0…10V (user configurable)

±5V (user configurable)

0…5V (user configurable)

Normal mode rejection ratio –
voltage or current terminal

-3 dB @ 12 Hz (300 Hz conversion rate)

-80 dB @ 50 Hz (300 Hz conversion rate)

-3 dB @ 6 Hz (150 Hz conversion rate)

-80 dB @ 60 Hz (150 Hz conversion rate)

Common mode rejection ratio -120 dB @ 50/60 Hz

Step response to 63% –
voltage or current terminal

1200 Hz conversion rate = 0.6 ms

600 Hz conversion rate = 6.7 ms

300 Hz conversion rate = 13.4 ms

150 Hz conversion rate = 26.7 ms

Input resistance

Voltage terminal

Current terminal


>10 M



<100

(2)

Absolute accuracy

(1)

Voltage terminal

Current terminal


0.1% full scale @ 25 °C

0.1% full scale @ 25 °C

Accuracy drift w/temperature

Voltage terminal

Current terminal


0.0028% full scale/°C

0.0038% full scale/°C

(1)

Includes offset, gain, non-linearity and repeatability error terms.

(2)

If 24V DC is removed from the module, input resistance = 10 k

Output Specifications

Attribute

Value

Number of outputs

2 isolated

Resolution

Voltage

Current

15 bits plus sign

0.320 mV/cnt

0.656

A/cnt

General Specifications

Data format

2’s complement

2’s complement %

Binary

Offset binary

Conversion type

Digital-to-analog converter

Update rate

2.5/5.0 ms all channels (see

Update Rate for Real Time Sample Interval = 0

table)

Output current terminal

0 mA output until module is configured

4…20 mA (user configurable)

0…20 mA (user configurable)

Output voltage terminal

0V output until module is configured

±10V (user configurable)

0…10V (user configurable)

±5V (user configurable)

0…5V (user configurable)

Step response to 63%of full
scale

<25

s

Current load on voltage
output, max

3 mA

Resistive load on voltage
output

0…750

Absolute accuracy

(1)

Voltage terminal

Current terminal


0.1% full scale @ 25 °C

0.1% full scale @ 25 °C

Accuracy drift w/temperature

Voltage terminal

Current terminal


0.0028% full scale/°C

0.0038% full scale/°C

(1)

Includes offset, gain, non-linearity and repeatability error terms.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, surrounding air,
max.

55 °C (131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on power ports

±2 kV @ 5 kHz on shielded signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±2 kV line-earth(CM) on shielded signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Output Specifications

Advertising