Rockwell Automation 1794-IF2XOF2IXT FLEX XT I/O Isolated Input Analog Module User Manual

Page 5

Advertising
background image

5

Publication 1794-IN129B-EN-P - April 2009

General (Output)

Attribute

Value

Number of outputs

4 isolated (1794-OF4IXT)

2 isolated (1794-IF2XOF2XT)

Resolution

Voltage

Current

15 bits plus sign

0.320 mV/cnt

0.656

μ

A

/

cnt

Update rate

2.5/5.0/7.5 ms all channels (see input update rate table)

2.5/5.0 ms all channels (see input update rate table) (1794-OF4IXT)

Output current terminal

0 mA output until module is configured

4…20 mA (user configurable

0…20 mA (user configurable

Output voltage terminal

0V output until module is configured

±10V user configurable)

0…10V user configurable)

±5V user configurable)

0…5V user configurable)

Current load on voltage
output

3 mA maximum

Resistive load on current
output

0…750

Ω

General

Attribute

Value

Module location

Cat. No. 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, 1794-TB3TS,
and 1794-TBN

Data format

2’s complement

2’s complement %

binary

offset binary

Conversion type

Sigma Delta

Digital to analog converter (1794-OF4IXT)

Update rate

2.5/5.0/7.5 ms all channels (see input update rate table)

2.5/5.0 ms all channels (see input update rate table) (1794-OF4IXT)

Normal mode rejection ratio
- voltage or current Terminal

-3 dB @ 12 Hz (300 Hz conversion rate)

-80 dB @ 50 Hz (300 Hz conversion rate)

-3 dB @ 6 Hz (150 Hz conversion rate)

-80 dB @ 60 Hz (150 Hz conversion rate)

Common mode rejection
ratio

-120 dB @ 50/60 Hz

Step response to 63% -
voltage or current terminal
(1794-IF4IXT,
1794-IF2XOF2XT)

1200 Hz conversion rate = 0.6 ms

600 Hz conversion rate = 06.7 ms

300 Hz conversion rate = 13.4 ms

150 Hz conversion rate = 26.7 ms

Step response to 63% of full
scale (1794-OF4IXT,
1794-IF2XOF2XT)

< 25

μ

s

Absolute accuracy

(1)

voltage terminal

current terminal

0.1% Full Scale @ 25 °C

0.1% Full Scale @ 25 °C

Accuracy drift with
temperature

Voltage terminal

Current terminal

0.0028% Full Scale/°C (1794-IF4IXT, 1794-IF2XOF2XT)

0.0012% Full Scale/°C (1794-OF4IXT)

0.0038% Full Scale/°C (1794-IF4IXT, 1794-IF2XOF2XT)

0.0025% Full Scale/°C (1794-OF4IXT)

Calibration required

Factory calibrated. Can be calibrated in field when necessary

Maximum overload

30V continuous or 32 mA continuous, one channel at a time.

Indicators

1 red/green power/status indicator

Isolation voltage

120V (continuous), Basic Insulation Type, when used with 1794-TB2,
1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS

250V (continuous), Basic Insulation Type, when used with 1794-TBN

Type tested at 1500V AC for 60 s and Routine tested at 2550V DC for
1 s, between channel to power, channel to system, and power to
system, and channel to channel

Flexbus current

50 mA

Power dissipation

2.0 W maximum @ 31.2V DC

Thermal dissipation

Maximum 6.8 BTU/hr @ 31.2V DC

Keyswitch position

3 (1794-IF4IXT)

4 (1794-OF4IXT)

5 (1794-IF2XOF2XT)

External DC Power Supply
voltage

Voltage range

Supply current

24V DC nominal

19.2…31.2V DC (includes 5% AC ripple)

80 mA @ 24V DC (1794-IF4IXT)

210 mA @ 24V DC (1794-OF4IXT)

150 mA @ 24V DC (1794-IF2XOF2XT)

Dimensions

46 mm x 94 mm x 75 mm (1.8 in. x 3.7 in. x 2.95 in.) with module
installed in base

Wire size

Determined by installed terminal base

Wiring category

(2)

2 - on signal ports
2 - on power ports

Wire type

Shielded on signal ports

Enclosure

None (open-style)

Terminal screw torque

Determined by installed terminal base

North American temp code

T4

IEC temp code

T4

(1)

Includes offset, gain, nonlinearity and repeatability error terms.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1.

Environmental

Attribute

Value

Operating
temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…70 °C (-4…158 °F)

Non-operating
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative
humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Operating shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Non-operating
shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

General

Attribute

Value

Advertising