Industrial Automation Wiring and Grounding Guidelines

11

Publication 1770-4.1 – February 1998

Connect one input directly to the L1 side of the line, on the load side
of the CRM contacts, to detect whether the CRM contacts are
closed. In the ladder logic, use this input to hold off all outputs
anytime the CRM contacts are open. (Refer to your programming
manual.) If you fail to do this, closing the CRM contacts could
generate transient emi because outputs are already turned on. To
have outputs turned on when CRM contacts are closing would be
analogous to squeezing the trigger on a hand tool as you’re plugging
it in.

Figure 8
Ungrounded ac Power-Distribution System with
Master-Control Relay

Notes:

1

2

To minimize emi generation, connect a suppressor across an inductive load. For suppressors to use, refer to 11 and C
or the Electrocube catalog.

In many applications, a second transformer provides power to the input circuits and power supplies for isolation
from the output circuits.

+ -

Output
Actuator

CRM

Back-panel
Ground Bus

FUSE

FUSE

Multiple E-stop switches

Start

CRM

CRM

GND

L1

N or L2

CRM

19240

CRM

X

1

X

2

1LT

2LT

Step-down
Transformer

2

1FU

L1

2FU

L2

3FU

L3

L1

L2

L3

Disc.

H

1

H

2

H

3

H

4

The I/O circuits form a net
inductive load switched by the
CRM contacts. Therefore, a
suppressor is needed
across the line at the load side
of the CRM contacts.

Suppressor

3

Suppressor

1

3

Connect a suppressor here to minimize emi generation from the net inductive load switched by the CRM contacts. In
some installations, a 1

m

f 220

W

suppressor (Allen-Bradley 700-N5) or 2

m

f 100

W

suppressor (Electrocube PN

RG1676-7) has been effective. For suppressors to use, refer to Figure 11 and Table C or the Electrocube catalog.

Suppressor

1

Grounding-electrode
Conductor to
Grounding-electrode
System

Equipment-
Grounding
Conductors

Controller

Power Supply

Connect when
applicable

To dc I/O
actuators/
sensors

User dc

Supply

Input
Module
Wiring
Arm

Output Module
Wiring Arm

Input
Sensor

Incoming

ac

Enclosure
Wall

To Motor
Starters