2 FLEX I/O D-Shell Terminal Base Units and Distribution Boards

Publication 1794-IN107A-EN-P - March 2005

FLEX I/O D-Shell Terminal Base Units

Mounting the Terminal Base Unit on a DIN Rail

1. Remove the cover plug (if used) in the male connector of the unit to which you

are connecting this terminal base unit.

2. Check to make sure the 16 pins in the male connector on the adjacent device are

straight and in line so that the mating female connector on this terminal base
unit will mate correctly.

3. Make certain the female connector (C) is fully retracted.

4. Position the terminal base unit on the 35 x 7.5 DIN rail (A) (A-B pt no.

199-DR1).

5. Rotate the terminal base onto the DIN rail with the top of the rail hooked under

the lip on the rear of the terminal base. Use caution to make sure that the
female flexbus connector does not strike any of the pins in the mating
connector.

6. For specific wiring information, refer to the installation instructions for the

module you are installing in this terminal base.

7. Repeat the above steps to install the next terminal base.

Description

1

Terminal base unit

2

Female flexbus connector

3

Module locking latch

4

Keyswitch - set to the position required for the installed module

5

Mounting holes for panel mounting

6

Male flexbus connector

7

Cover plug for male flexbus connector

8

Locking tab

9

D-shell connector -1794-TB37DS - 37 pin D-shell connector;

1794-TB62DS - 62 pin D-shell connector

10

User power connectors

ATTENTION

During mounting of all devices, be sure that all debris (metal chips,
wire strands, etc.) is kept from falling into the module. Debris that
falls into the module could cause damage on power up.

ATTENTION

Do not remove or replace a terminal base unit when power is applied.

Interruption of the flexbus can result in unintended operation or

machine motion.

ATTENTION

Do not force the terminal base into the adjacent base/adapter.

Forcing the units together can bend or break the hook and allow the

units to separate and break communication over the backplane.

3

2

6, 7

8

9

4

1

5

10

10

Position the terminal base at a slight angle and hooked over the

top of the DIN rail.

A

B

A

C

DIN rail

Slide the terminal base over tight against the adapter.

Make sure the hook (C) on the terminal base slides under

the edge of the adapter and the flexbus connector is fully retracted.

Press down on the terminal base to lock it on the DIN rail.

If the terminal base does not lock into place, use a screwdriver or

similar device to open the locking tab, press down on the base, and

release the locking lever to lock the base in place.

Gently push the flexbus connector into the side of the adapter

to complete the backplane connection.