Page 58: Diagnostic words in the btr file

6–2
Troubleshoot the CFM Module
Publication 1771Ć6.5.99 - December 1995
The CFM module returns diagnostics to the PLC processor in words
one and two of the BTR file. These diagnostics give you the number
of the word in the BTW configuration block that has caused an error
to occur.
Important: In the event that there are multiple incorrect
BTW words, the CFM module only returns the first
incorrect word.
Diagnostic Words in the BTR File
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
PowerĆup Bit indicates if a
valid BTW has occurred since
powerĆup or since last
switched from Program to
Run mode.
Header (CFM module ID)
must be 0010.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Error Words & Diagnostics displays
invalid BTW word number (0Ć60 BCD).
99 = invalid BTW length
Output Status reflects current
operating state of outputs.
b12 = Output 0 b13 = Output 1
b14 = Output 2 b15 = Output 3
VALUES:
0 = OFF
1 = ON
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
word 2
word 1
ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ
0
0
1
0
VALUES: 1= no or invalid BTW
0 = yes
To find out more about the CFM module:
specifications on the CFM module
See appendix
For
Specifications
Schematics
input and output circuit drawings
A
B
Diagnostics
What's Next