Driving inputs with outputs – Rockwell Automation 1771-IGD TTL Input Module Installation Instructions User Manual
Page 10

TTL Input Module
10
Publication 1771ĆIN022B-EN-P - September 2002
dc common
+5V dc
Input 00
Input 01
Input 02
Input 03
Input 04
Input 05
Input 06
Input 07
Customer Class 2
Power Supply
+5V dc
+
-
Ground cable shield at the chassis
grounding stud or by using singleĆpoint
grounding
2
3
3
2
2
3
TTL Devices must have openĆcollector outputs.
Internal or external pullĆup resistor (1K ohm typical).
(See applicable codes and laws.)
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
Input 17
+5V dc
+5V dc
+5V dc
(Actual wiring runs in this direction.)
A
B
C
D
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
E
10450ĆI
1
1 You can make this connection to terminal A, B, C or D.
Field Wiring Arm
Cat. No. 1771ĆWH
Do not exceed the specified isolation voltage when using multiple power sources.
7. Connect TTL output devices using Belden 8761 shielded cable as
shown in the connection diagram. Do not exceed 50 cable feet for
any output device. Connect the insulated wires to their respective
terminals on the field wiring arm.
Driving Inputs with Outputs
Input terminals of the TTL input module (cat. no. 1771-IGD) may be
directly driven by the outputs of a TTL output module (cat. no.
1771-OGD). Connect the cable shield between modules at one end
only.