Rockwell Automation 1734-EPAC POINT I/O ac Power Supply User Manual

Page 15

Advertising
background image

POINT I/O 120/240V ac Expansion Power Supply 15

Publication

1734-IN017A-EN-P - December 2005

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz

10V/m with 200 Hz 50% pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz

EFT/B Immunity

IEC 61000-4-4:

±4 kV at 5 kHz on power ports

Surge Transient Immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports

Conducted RF Immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from

150 kHz…80 MHz

Emissions

CISPR 11

Group 1, Class A

Enclosure Type Rating

None (open-style)

Voltage Variation

30% dips for 1 period at 0 ° & 180 ° on ac supply ports

60% dips for 5 and 50 periods on ac supply ports

±10% fluctuations for 15 minutes on ac supply ports

>95% interruptions for 250 periods on ac supply ports

Conductors Wire

Size

Category

14…22 AWG (2.5…0.34 mm

2

) - solid or stranded copper wire

rated at 75 °C or greater

1.2 mm (3/64 inch) insulation maximum

1

(1)

on power ports

Terminal Base Screw Torque 0.8 Nm (7 lb-in)

Field Wiring Terminations

0 - No Connection

1 - No Connection

2 - Protective Earth Ground

3 - Protective Earth Ground

4 - L2/N

5 - L2/N

6 - L1

7 - L1

Weight Metric

Imperial

182 g

6.40 oz