Digital output terminals – Rockwell Automation 1753-L28BBB-M_P GuardPLC 1600 Controllers User Manual

Page 11

Advertising
background image

11

Rockwell Automation Publication 1753-IN001C-EN-P - June 2010

Digital Output Terminals

Terminals accommodate wires up to 1.5 mm

2

(16 AWG). See the terminal torque specifications

on page

17

. Digital outputs are connected to these terminals.

For connection of a load, the reference pole L- of the corresponding channel group must be used
(2-pole connection). Although L- at terminals 1 and 6 and at 7 and 12 is connected internally to
L- on the power supply input, it is strictly recommended to use 1 and 6 for outputs 1…4 only and
7 and 12 for outputs 5… 8 only. EMC testing was performed in this manner.

Terminal Number

Designation

Function

Current

1

L-

Reference pole

2

1

Digital output 1

0.5 A

3

2

Digital output 2

0.5 A

4

3

Digital output 3

0.5 A

5

4

Digital output 4 (for increased load)

2.0 A

6

L-

Reference pole

7

L-

Reference pole

8

5

Digital output 5

0.5 A

9

6

Digital output 6

0.5 A

10

7

Digital output 7

0.5 A

11

8

Digital output 8 (for increased load)

2.0 A

12

L-

Reference pole

1 2 3 4 5 6

1 2 3 4

1

L-

L-

DO

2

(2A)

3 4

5 6

7 8 9 10 11 12

7 8 9 10

5

L-

L-

DO

6

(2A)

7 8

11 12

Advertising