Removing the terminal block, Input and output connections, Encoder wiring – Rockwell Automation 1746-HSCE2 Multi-Channel High-Speed Counter Installation Instructions User Manual
Page 10

10 Multi-Channel High-Speed Counter
Publication 1746-IN002A-US-P
Removing the Terminal Block
Remove the terminal block by turning the slotted terminal block release screws
counterclockwise. The screws are attached to the terminal block, so the block
will follow as the screws are turned out.
Input and Output Connections
Input and output wiring terminals are shown in the figure below. Each terminal
accepts two #14 AWG wires. Tighten screws only tight enough to immobilize the
wire. The torque applied to the screw should not exceed 0.9 Nm (8 in-lb).
Encoder Wiring
Differential encoders provide the best immunity to electrical noise. We
recommend, whenever possible, to use differential encoders.
The wiring diagrams on the following pages are provided to support the
Allen-Bradley encoders you may already own.
!
ATTENTION
To avoid cracking the removable terminal block, alternate
removal of the slotted terminal block release screws.
B1-
A1-
A2-
Z1-
Z2-
B2-
OUTPUT 2
OUTPUT 0
+Vdc
B1+
A1+
A2+
Z1+
Z2+
B2+
OUTPUT 1
OUTPUT COMMON
OUTPUT 3
Release Screw
Release Screw