Rockwell Automation 1756-L53 Logix5553 Controller Installation Instructions User Manual
Page 8

8 Logix5553 Controller
Publication 1756-IN017A-EN-P - August 2000
2. Attach the battery label:
a. Write on the battery label the date you install the battery.
b. Attach the label to the inside of the controller door.
ATTENTION
!
ATTENTION
!
To prevent possible battery leakage, you must replace a
battery, even if it is still good, according to the following
schedule:
ATTENTION
!
ATTENTION
!
Store batteries in a cool, dry environment. We recommend 25
°
C
with 40% to 60% relative humidity. You may store batteries for
up to 30 days between -45
°
to 85
°
C, such as during
transportation. To avoid possible leakage, do not store batteries
above 60
°
C for more than 30 days.
41025
battery label
If the rack inlet temperature is:
Replace the battery within:
0
°
to 35
°
C
No required replacement
36
°
to 40
°
C
3 years
41
°
to 45
°
C
2 years
46
°
to 50
°
C
16 months
51
°
to 55
°
C
11 months
56
°
to 60
°
C
8 months