Remove the Adapter From the Mounting Base
Follow the instructions to remove the adapter from the mounting base.
1. Put a flat blade screwdriver into the slot of the orange latching
mechanism.
2. Push the screwdriver toward the I/O module to disengage the latch.
The module lifts up off the base.
3. Pull the module off the base.
Set the Network Address
Valid node addresses are 00…63.
Set the node address using either the rotary switches, RSNetWorx for 
DeviceNet, DeviceNetManager, or another software configuration tool. 
Setting the switches at any number from 64…99 allows the software to have 
address control.
Each module is shipped with the switches set for node address 63. Remove the 
caps on the front of the module to access the switches. The two switches are:
• X10 (most significant digit) – left side of module
• X1 (least significant digit) – right side of module
Network Node Example
To reset the node address, use a small blade screwdriver to rotate the switches. 
Line up the small notch on the switch with the number setting you wish to use 
and then cycle power.
The I/O adapter periodically reads the rotary switches. If the switches have 
changed since the last reading and they no longer match the online address, a 
This example shows 
the network address 
set at 63.