Mounting – Rockwell Automation 1762-OX6I MicroLogix 1200 Relay Output Module User Manual
Page 5
 
MicroLogix 1200 Isolated Relay Output Module 5
Publication 1762-IN017C-EN-P - May 2013
Mounting
Minimum Spacing
Maintain spacing from enclosure 
walls, wireways, adjacent 
equipment, etc. Allow 50.8 mm 
(2 in.) of space on all sides for 
adequate ventilation, as shown:
.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm 
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN rail 
mounting area of the module against the DIN rail. The latch will momentarily open and lock 
into place.
ATTENTION
!
Do not remove protective debris strip until after the module and all other 
equipment near the module is mounted and wiring is complete. Once 
wiring is complete and the module is free of debris, carefully remove 
protective debris strip. Failure to remove strip before operating can cause 
overheating.
TIP
1762 expansion I/O may be mounted horizontally only.
ATTENTION
!
During panel or DIN rail mounting of all devices, be sure that all debris 
(metal chips, wire strands, etc.) is kept from falling into the module. 
Debris that falls into the module could cause damage when power is 
applied to the module.
Side
Side
Top
Bottom