A - specifications, Electrical specifications, Environmental specifications – Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual
Page 65: Network specifications, Appendix a, Specifications

A
Appendix
A–1
Specifications
This appendix provides the following module and system specifications.
•
electrical specifications
•
environmental specifications
•
network specifications
It also discusses throughput time for the DCM.
Backplane Current Consumption
360mA at 5V
Operating Temperature
0
°
C to 60
°
C (32
°
F to 140
°
F)
Storage Temperature
−
40
°
C to
+
85
°
C (
−
40
°
F to
+
185
°
F)
Humidity Rating
5% to 95% noncondensing
Agency Certification
(when product or packaging is marked)
•
CSA certified
•
CSA Class I, Division 2
Groups A, B, C, D certified
•
UL listed
•
CE marked for all applicable directives
Baud Rate
Maximum Cable Distance
(Belden 9463)
Resistor Size
Us n
xten e
57.6K baud
10,000 feet at 57.6K baud
Using Extended
o e apab l t
115.2K baud
5,000 feet at 115.2K baud
82
W 1/2 Watt
Node Capability
230.4K baud
2,500 feet at 230.4K baud
82
W 1/2 Watt
Not Using
57.6K baud
3048 meters (10,000 feet)
1
W 1
Not Using
Extended Node
apab l t
115.2K baud
1524 meters (5,000 feet)
150
W 1/2 Watt
Extended Node
Capability
230.4K baud
762 meters (2,500 feet)
82
W 1/2 Watt
Electrical Specifications
Environmental Specifications
Network Specifications