Specifications – Rockwell Automation 1771-OBN DC (10-30V) Output Module Installation Instructions User Manual

Page 12

Advertising
background image

DC (10-30V) Output Module

12

Publication 1771ĆIN034B-EN-P - August 2002

Outputs per module

32 (4 groups of8)

Module Location

1771ĆA1B thru ĆA4B or later I/O Chassis

Voltage Rating

10 to 30V dc, 0.5A per output, 2A per group, 8A per module

Maximum Output Current

0.5A per output (not to exceed 8A per module)

2A per output group

Maximum Surge Current

2A per output for 10ms; repeatable every 2s.

5A per output group for 10ms.;repeatable every 2s.

20A per module for 10ms.; repeatable every 2s.

Maximum OnĆstate Voltage Drop

1.5V dc at 0.5A

Maximum OffĆstate Leakage

Current

1.0mA @ 55

o

C

Output Signal Delay On to Off

Off to On

2.0ms

0.1ms

Power Dissipation

13.7W (max); 1.7W (min)

Thermal Dissipation

46.7 BTU/hr (max); 5.7 BTU/hr (min)

Backplane Current

330mA @ 5V dc maximum

Isolation Voltage

Tested to withstand 500V dc for 60s

Fuses

Four 4.0A, 250V normal blow fuses (1 per group); SAN-O

Corporation ST4-4.0A

Conductors

Wire Size

Category

14-22 AWG (2.5-0.5mm

2

) (max) stranded copper rated at 60

o

C or

greater

3/64 inch (1.2mm) insulation (max)

2

1

Environmental Conditions

Operating

Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 131°F (0

o

to 60

o

C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal

Shock)

-40 to 185°F (-40 to 85

o

C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2

4kV indirect discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

10V/m with 200Hz 50% pulse 100% AM at 900MHz

EFT/B Immunity

IEC 61000-4-4

+2kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

+1kV line-line (DM) and +2kV line-earth (CM) on signal ports

Specifications continued on next page.

Specifications

Advertising