24 compactlogix analog output module – Rockwell Automation 1769-OF8V CompactLogix Analog Output Module User Manual
Page 24

24 CompactLogix Analog Output Module
Rockwell Automation Publication 1769-IN089A-EN-P - March 2011
Local:1:C.Ch1En
BOOL
Decimal
+
Local:1:C.Ch1Range
SINT
Decimal
+
Local:1:C.Ch1DataFormat
SINT
Decimal
+
Local:1:C.Ch1FaultValue
INT
Decimal
+
Local:1:C.Ch1ProgValue
INT
Decimal
+
Local:1:C.Ch1LClampValue
INT
Decimal
+
Local:1:C.Ch1HClampValue
INT
Decimal
+
Local:1:C.Ch1RampRate
INT
Decimal
Tag Name
To Select
Make These Bit Settings
(1)
15-8
7
6
5
4
3
2
1
0
Ch#ProgToFaultEn
Enable
1
Disable
0
Ch#HoldForInit
Enable
1
Disable
0
Ch#ProgMode
Enable
1
Disable
0
Ch#FaultMode
Enable
1
Disable
0
Ch#RampEn
Enable
1
Disable
0
Ch#AlarmLatchEn
Enable
1
Disable
0
Ch#OverRangeInterruptEn
Enable
1
Disable
0
Ch#UnderRangeInterruptEn
Enable
1
Disable
0
Ch#En
Enable
1
Disable
0
Ch#Range (1769-OF8C)
0…20 mA DC
0
4…20 mA DC
1
Ch#Range (1769-OF8V)
-10…+10V dc
0
0
0…5V dc
0
1
0…10V dc
1
0
1…5V dc
1
1