Arithmetic status flags, Fault conditions – Rockwell Automation Logix5000 Controllers Structured Text Programming Manual User Manual

Page 35

Advertising
background image

Publication 1756-PM007D-EN-P - November 2012

35

Program Structured Text Chapter 1

These diagrams show how a REPEAT...UNTIL loop executes and how an
EXIT statement leaves the loop early.

Arithmetic Status Flags:

Not affected

Fault Conditions:

Example 1:

While the bool_expression is false, the controller
executes only the statements within the
REPEAT…UNTIL loop.

To stop the loop before the conditions are false, use
an EXIT statement.

Statement 1

Statement 2

Statement 3

BOOL expression

False

True

Rest of the routine

BOOL expression

False

True

Rest of the routine

Statement 1

Statement 2

Statement 3

Yes

No

A major fault will occur if

Fault type

Fault code

The construct loops too long

6

1

If you want this

Enter this structured text

The REPEAT...UNTIL loop executes the statements in the
construct and then determines if the conditions are true before
executing the statements again.

This differs from the WHILE...DO loop because the WHILE...DO
The WHILE...DO loop evaluates its conditions first. If the
conditions are true, the controller then executes the
statements within the loop. The statements in a
REPEAT...UNTIL loop are always executed at least once. The
statements in a WHILE...DO loop might never be executed.

pos := -1;

REPEAT

pos := pos + 2;

UNTIL ((pos = 101) OR (structarray[pos].value = targetvalue))

end_repeat;