Ground the Chassis

This I/O chassis

Has grounding stud(s) located

1771-A2BSS
1771-A3B1SS

ATTENTION: To prevent ground loops from
occurring, use only one grounding stud when
grounding your equipment.

Important:

Use the following information, along with the
installation manual for your programmable controller to
ground the I/O chassis and your I/O modules.

Chassis Ground

Single-point Grounding

I/O chassis side plate

star washer

nut with captive washer

ground lug

1

ground lug

nut with captive washer

When you connect grounding conductors to the I/O chassis
grounding stud, place a star washer under the first lug, then
place a nut with captive lock washer on top of each ground lug.

grounding stud

1

Use the cup washer if crimp-on lugs are not used.

#10 thread-forming screw

external-tooth washers

19923

ATTENTION: Use single-point grounding for
extended-local I/O systems. The systems must be
grounded properly for proper performance.