Use controlflash – Rockwell Automation 1747-DU501 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Installation User Manual
Page 5

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 5
Publication 1747-IN019G-EN-P - December 2011
This returns the processor to the initial factory conditions.
Use ControlFLASH
1.
Launch the ControlFLASH application under Programs>Flash Programming Tools.
2.
Verify that the J4 jumper of the SLC 5/05 processor being upgraded is set to Protect.
The daughtercard firmware can only be updated when the J4 jumper is set to Protect.
ATTENTION: Do not interrupt the flash procedure. Once you have begun to download the
firmware for either the daughtercard (step 18) or the motherboard (step 24), the SLC 5/05 is
put into an unrecoverable state if you lose power or communications for any reason.