Using This Manual
Chapter 1
1Ć3
Table 1.A
Compatibility and Use of Data Table
Catalog
Number
Use of Data Table
Input Output Read Write
Image Image Block Block
Bits Bits Words Words
Compatibility
Addressing Chassis
1/2 -slot 1-slot 2-slot
Series
1771-IR
Series B
8
8
8/9
14/15
Yes
Yes
Yes
A and B
A = Compatible with 1771-A1, A2, A4 chassis.
B = Compatible with 1771-A1B, A2B, A3B, A4B chassis.
Yes = Compatible without restriction
No = Restricted to complementary module placement
You can place your input module in any I/O module slot of the I/O chassis. You
can put:
two input modules in the same module group
an input and an output module in the same module group.
Do not put the module in the same module group as a discrete high density
module unless you are using 1 or 1/2 slot addressing. Avoid placing this module
close to AC modules or high voltage DC modules.
For a list of publications with information on Allen–Bradley programmable
controller products, consult our publication index SD499.