14 Compact TTL Input Module

Publication 1769-IN079A-EN-P - May 2006

Configuration File

The read/writable configuration data file allows the setup of the digital filter settings
for each of the two input groups. Group 0 is inputs 0…7, Group 1 is inputs 8…15.

The manipulation of the bits from this file is normally done with programming
software (for example, RSLogix 500 or RSNetworx for DeviceNet software) during
initial configuration of the system. In that case, graphical screens are provided via
the programmer to simplify configuration. However, some systems (for example,
1769-ADN DeviceNet Adapter) also allow the bits to be altered as part of the
control program using communication rungs. In that case, it is necessary to
understand the bit arrangement.

Configuration File

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Filter Time On to Off

Group 1

Filter Time Off to On

Group 1

Filter Time On to Off

Group 0

Filter Time Off to On

Group 0

1

0000000000000000

2

0000000000000000

3

0000000000000000

Filter Time

Filter Time

(1)

(1)

Filter Time:

Word 0, the Filter

Time configures the ON to OFF
and OFF to ON hardware delay
times for each input group.

Bit Setting

8.0 ms

0000

4.0 ms

0001

2.0 ms

0010

1.0 ms

0011

0.5 ms

0100

0.1 ms

0101

0.0 ms

0110