Setting the 1794-IM8 Input Filter Time

To select your input filter time (FT) for channels 00-07, set the corresponding
bits in the output image table (complementary word) for the module.

Input Filter Time for the 1794-IM8

For example, setting bits 00, 01 and 02 as shown below sets the off-to-on filter
time for inputs 00 thru 07 to 12ms. For other settings, refer to the Input Filter
Time table above.

Specifications

Bits

Description

Selected

Filter

Time

Maximum Filter

Time (ms)

02

01

00

Filter Time - inputs 00-07

Off to On

On to Off

0

0

0

Filter Time 0 (Default)

256

µ

s

7.5

26.5

0

0

1

Filter Time 1

512

µ

s

8

27

0

1

0

Filter Time 2

1ms

9

28

0

1

1

Filter Time 3

2ms

10

29

1

0

0

Filter Time 4

4ms

12

31

1

0

1

Filter Time 5

8ms

16

35

1

1

0

Filter Time 6

16ms

24.5

44

1

1

1

Filter Time 7

32ms

42

60.5

Specifications

220V ac Input Module, Cat. No. 1794-IM8

Number of Inputs

8, (1 group of 8), nonisolated

Module Location

Cat. No. 1794-TBN

Module Mounting

See Derating Curve

On-state Voltage

159V ac minimum
220V ac nominal
264V ac maximum

On-state Current

5.27mA minimum @ 159V ac, 47Hz
9.88mA nominal @ 220V ac, 60Hz
13.21mA maximum @ 264V ac, 63Hz

Off-state Voltage

40V ac maximum

Off-state Current

2.6mA maximum

Input Impedance

22.3K ohms nominal

Nominal Input Current

10mA @ 220V ac, 60Hz

Isolation Voltage

Tested at 2600V dc for 1s between user and system
No isolation between individual channels

No isolation between customer power and input channels

Input Filter Time

1

Refer to Input Filter Time table

Flexbus Current

30mA @5V dc

Power Dissipation

4.7W maximum @ 264V ac

Thermal Dissipation

Maximum 16.2 BTU/hr @ 264V ac

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

FT = 0-07

O:010

Dec.

FLL

I:000

00

Fill File
Source
Destination
Length

#O:010

1

Write FT to complement

of input module.

Write filter time on system startup.

7

6

5

4

3

2

1

0

0

1

0

= 4 Octal or 4 Decimal

1794-IM8

Specifications

220V ac Output Module Cat. No. 1794-OM8

Number of Outputs

8, (1 group of 8), nonisolated

Module Location

Cat. No. 1794-TBN, -TBNF

Module Mounting

See Derating Curve

Output Current Rating

4.0A (8 outputs @ 500mA)

On-state Current

50mA per output minimum
500mA per output maximum @ 55°C

On-state Voltage Drop

maximum 1.5V ac @ 0.5A

Surge Current

7A for 40ms, repeatable every 8s

Off-state leakage

2.5mA maximum

Isolation Voltage

Tested at 2600V dc for 1s between user and system
No isolation between individual channels

No isolation between customer power and output channels

Output Signal Delay Time

2

Off to On

On to Off

1/2 cycle maximum

1/2 cycle maximum

Flexbus Current

60mA @5V dc

Power Dissipation

5.0W maximum @ 0.5A

Thermal Dissipation

Maximum 17.1 BTU/hr @ 0.5A

Fusing (when using the
1794-TBNF)

3

0.8A, 250 slow-blow fuse

(5 X 20mm SAN-O MQ4-800mA)

General Specifications

Terminal Base Screw
Torque

9 pound-inches (1.0Nm)

Dimensions (with module
installed)

3.7H x 3.7W x 2.7D inches
94H x 94W x 69D mm

Indicators (field side
indication, customer
device driven)

1794-IM8 - 8 yellow status indicators, customer device driven

1794-OM8 - 8 yellow status indicators, logic driven

External ac power
Supply voltage

Input Frequency
Voltage range

220V ac nominal
47-63Hz

159 to 264V ac

Refer to Derating Curves below.

Keyswitch Position

8

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

±2kV at 5kHz on power ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)