Rockwell Automation 1734-8CFGDLX POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix IN User Manual
Page 16

16 POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix
Publication
1734-IN039A-EN-P - March 2009
You can select other consumed assemblies:
•
Consumed assembly instance 34 is the first byte of consumed
assembly instance 102 (Data [0]).
•
Consumed assembly instance 112 is the first eight bytes of consumed
assembly instance 102 (Data [0]…[7]).
In RSLogix5000, the default tags will be:
•
AdapterName:SlotNumber:O.Data
•
AdapterName:SlotNumber:O.LogicDefinedData
•
AdapterName:SlotNumber:O.LogicDefinedIntData[0...7]
Data Map - Configuration Assembly Instance 123
Message Size: 48 Bytes
Bit
7
6
5
4
3
2
1
0
Data [0]
Group Off2On Input filter
Data [1]
Data [2]
Group On2Off Input filter
Data [3]
Data [4]
FltM 7
FltM 6
FltM 5
FltM 4
FltM 3
FltM 2
FltM 1
FltM 0
Data [5]
FltV 7
FltV 6
FltV 5
FltV 4
FltV 3
FltV 2
FltV 1
FltV 0
Data [6]
IdlM 7
IdlM 6
IdlM 5
IdlM 4
IdlM 3
IdlM 2
IdlM 1
IdlM 0
Data [7]
IdlV 7
IdlV 6
IdlV 5
IdlV 4
IdlV 3
IdlV 2
IdlV 1
IdlV 0
Data [8]
Reserved
RACK
CFO
DM
MP
Data [9]
Reserved
Data [10]
Masterless Produce Assembly Instance (0, 4, 101, 111)
Data [11]
Data [12]
Masterless Produce EPR (ms)
Data [13]