Rockwell Automation 1790-TXXXX CompactBlock LDX I/O Profibus Analog, RTD and Thermocouple User Manual
Page 21

21
Publication 1790-IN010B-EN-P - April 2003
RTD and Thermocouple Blocks - I/O Channel LED Status Indicator
Status:
Description:
Flashing Green/Red
Power up
Off
Off line
Red
On line and no field power
Red
PROFIBUS connection and no field power
Flashing Red
Field power and open wire
Green
Field power and valid input
Flashing Red
Input over range
Flashing Red
Input under range
Flashing Red
Recoverable fault
I/O Channel LED Status Indicator
1790D-TN4C0
1790D-TN0C2
Status:
Description:
Status:
Description:
Flashing Green/
Red
Power up
Flashing Green/
Red
Power up
Off
Off line
Off
Off line
Red
On line and no field
power
Off
On line and no field
power
Red
PROFIBUS connection
and no field power
Green
PROFIBUS connection
and no field power
Flashing Red
1
Field power and open
wire (4-20mA range
only)
2
Green
Field power and open
wire
Green
Field power and valid
input
Green
Field power and valid
output
Green
Input over range
Flashing Red
Field power and
output out of range
Flashing Red
1
Input under range
<3mA (4-20ma
range only)
2
Flashing Green
Output idle
Flashing Red
Recoverable fault
Flashing Red
Recoverable fault
1
Green for 0-20mA range.
2
Can be determined from the data table.