Operation and Troubleshooting

Appendix A

AĆ5

The interface has an EXIT REQ pushbutton switch on its front panel.
When you press this switch, the interface sends out a signal to the other
nodes of the Data Highway II link that it no longer wants to be included in
the logical ring After exiting, the interface turns on the EXIT COMP
LED. The other nodes will not attempt to pass the token to this node unit
it is reset

Use the EXIT REQ switch before turning off interface power. If you do
not, the other nodes will waste time trying to reconstruct the ring after
being unable to pass the token to this node.

When you suspect that the KP3 module is not functioning properly, follow
the steps in the table below.

Step:

If:

Then:

1. Check the FAIL LED indicator.

ON

replace the KP3 module.

OFF

go to step 2.

2. Check the DUP ADDR indicator

ON

follow these steps:

a. Turn the PLC-3 power OFF.

b. Set a unique node address for the node

using the thumbwheels switches.

c. Turn the PLC-3 power ON.

OFF

go to step 3.

3. Check the IN-RING.SEEKING-MEM

LED indicator.

yellow

check the cabling on the Data Highway II link.

green

go to step 4.

4. Check the ERROR LED indicator.

flashing

check the message instruction in the ladder

diagram program for an error code beside the

control file address. You can look up the error

code in Appendix B.

OFF

check the ladder diagram program for proper

use of the message instruction, and check the

PLC-3 mode (no messages can be sent in

program mode).

If you are still experiencing problems after troubleshooting attempts fail,
contact your local Allen–Bradley Integrator or Sales office.

Using the Exit Request Switch

Troubleshooting the KP3

Advertising