Environmental specifications – Rockwell Automation 1757-PLX52 ProcessLogix Controller Module Installation Instructions User Manual
Page 13

Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0
… 60 °C (32… 140 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40
… 85 °C (-40… 185 °F)
Barometric pressure
Altitude, -300
… 2000 m
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5
… 95% non-condensing
(1)
The maximum relative humidity specification applies up to 40 °C (140 °F). Above 40°C (140 °F) the RH specification is
de-rated to 55% to maintain constant moisture content.
(1)
Vibration
IEC 60068-2-6 (Test Fc, Operating):
0.5 g @ 10
… 60 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 5 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 20 g
Enclosure required
Yes
Enclosure type rating
None (open-style)
North American temperature code
T4A
ProcessLogix Controller 13
Publication 1757-IN901D-EN-P - May 2007