Table a – Rockwell Automation 2100 CENTERLINE MCC Joining Splicing Vertical Sections User Manual

Page 14

Advertising
background image

AMP

MATERIAL

QTY

THICKNESS

WIDTH SPLICE MTG. HOLES

600

Copper/Tin

1

.125”

3”

2

Copper/Silver

1

.125”

Aluminum/Tin

1

.125”

4”

800

Copper/Tin

1

.125”

4”

2

Copper/Silver

1

.125”

Aluminum/Tin

1

.1875”

1200

Copper/Tin

1

.250”

4”

2

Copper/Silver

1

.250”

1600

Copper/Tin

2

.250”

4”

4

Copper/Silver

2

.250”

2000

Copper/Tin

1

.250”

4”

4

1

.375”

Copper/Silver

1

.250”

4”

4

1

.375”

2500/
3000

Copper/Tin

2

.375”

4”

4

Copper/Silver

2

.375”

14 CENTERLINE

®

2100 Motor Control Centers Joining and Splicing Vertical Sections

Figure 13 Insulated “Z” 600 - 1200 Amp Bus Splicing Detail and Configuration
Example

Main Horizontal Bus or
Neutral Bus (5” Deeper)

Main Horizontal Splice

One-piece assembly of
nut and conical spring

Bus Clamps

washer

Insulated

Splice Kit Configuration Example

Front

(Top View - 3 Sections)

Main Horizontal Splice or Neutral

Flat Washers

Bus (standard location)

Refer to Table A for bus size and thickness.

Table A Bus and Splice Bar Dimensions