Rockwell Automation 61C346 4 Input 0-10V Analog Rail Module User Manual
Page 19

3Ć5
Channel 0
Channel 1
Channel 2
Channel 3
Common
1
2
3
Common
4
5
6
+
-
I
Source
VĆIn
Common
7
8
9
+
-
I
Source
VĆIn
Common
10
11
12
+
-
I
Source
VĆIn
+
-
I
Source
VĆIn
Figure 3.2 ĆTypical Recommended Input Shielding Methods
Step 11. Turn off power to the Reliance device that will be
connected to the Analog Rail module.
Step 12. Set the Mode" switch on the faceplate of the module to
the desired position.
Step 13. Connect the I/O Rail cable between the Analog Rail
connection labeled Input" and an I/O port on the
Reliance device that will communicate with the module.
Turn on power to the Reliance device that will
communicate with the module. Recall that the Mode
switch is read each time the Reliance device connected to
the Analog Rail module is powered up.
Step 14. The Analog Rail installation is now ready for testing.
Inspect all work to assure that the installation has been
performed properly.
Step 15. Turn on power to the Input Power" wiring. Turn on power
to the external hardware. See Appendix A for power
supply specifications.
Step 16. Verify that the hardware has been installed correctly.
Before testing, insure that the external hardware will not
respond to output signals from the Analog Rail module.