CENTERLINE Motor Control Centers Install External Auxiliary Contact Adapter

About the Auxiliary Contact
Adapter

Use these instructions to install an external auxiliary contact adapter in
CENTERLINE 2100 Series Q…Y units with Cutler-Hammer Westinghouse
Circuit Breakers

(1)

(HMCP600, LD, HLD, LDC, MDL, HMDL, ND, HND,

and NDC).

This auxiliary contact kit (2100H-N23) is to be used with the following auxiliary
contacts: catalog numbers 2100H-N19 or 2100H-N20.

Required Tools

You need a socket set with extension and a torque wrench to complete the
installation.

Install the Auxiliary Contact
Adapter

Follow these steps and refer to

Assembly of External Auxiliary Contact Parts

to

install the auxiliary contact adapter.

1. Verify that all power has been disconnected and turn operator handle to

the OFF/O position.

2. Verify the parts list, see

Assembly of External Auxiliary Contact Parts

.

3. Attach the external auxiliary contact assembly to the mounting plate by

using two 1/4-20 thread-rolling screws and torque to 55 lb•in (6.2 N•m).

Refer to

Assembly of External Auxiliary Contact Parts.

4. Attach the actuator to the circuit breaker bail by using two 1/4-20

thread-rolling screws.

5. Position the actuator so the screws are centered in slots and torque to

55 lb•in (6.2 N•m).

6. Install auxiliary contacts (Catalog Number 2100H-N19 or 2100H-N20).
7. Turn operator handle to ON/I position to be sure that the auxiliary

contacts change state.

8. Check continuity to be sure proper operation of auxiliary contacts.

(1) These circuit breakers are available for Bulletin 2100 Series Y and earlier motor control centers.

ATTENTION: De-energize all power sources to the motor control center before
installing auxiliary contact adapter. Failure to de-energize all power sources can
result in severe injury or death.