Field wiring connections, Wire the outputs, Specifications – Rockwell Automation 2085-OW8_OW16 Micro800 8-Point and 16-Point AC/DC Relay Output Modules User Manual

Page 9: General specifications

Advertising
background image

Micro800 8-Point and 16-Point AC/DC Relay Output Modules 9

Publication 2085-IN004A-EN-P - September 2012

Field Wiring Connections

In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI).

Wire the Outputs

Included with your 2085-OW8 module is a single 12-pin Removable Terminal Blocks (RTB).
Included with your 2085-OW16 module are two 12-pin RTB. Basic wiring of your module is
shown below.

Basic Wiring to the Module

Specifications

ATTENTION: Do not wire more than 2 conductors on any single terminal.

General Specifications

Attribute

2085-OW8

2085-OW16

Number of Outputs

8

16

Dimensions
HxWxD

28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)

44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)

Shipping weight, approx.

140 g (4.93 oz)

220 g (7.76 oz)

Wire size

0.25... 2.5 mm

2

(22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ), or greater,

1.2 mm (3/64 in.) insulation max

CM0

O-00

O-01

CM1

O-02

O-03

CM2

O-04

O-05

CM3

O-06

O-07

L1 or +DC

L2 or -DC

45310

CM0

O-00

O-01

CM1

O-02

O-03

CM2

O-04

O-05

CM3

O-06

O-07

CM4

L1 or +DC

L2 or -DC

O-08

O-09

CM5

O-10

O-11

CM6

O-12

O-13

CM7

O-14

O-15

45311

2085-OW8

2085-OW16

Terminal Block 1

Terminal Block 2