General specifications – Rockwell Automation 2085-IA8_IM8_OA8 Micro800 8-Point Input and 8-Point Output AC Modules User Manual

Page 10

Advertising
background image

10 Micro800 8-Point Input and 8-Point Output AC Modules

Publication 2085-IN005B-EN-P - September 2012

Status indicators

8 yellow indicators

Isolation voltage

150V (continuous), Reinforced
Insulation Type, channel to
system
Type tested at 1950V DC for 60 s

240V (continuous), Reinforced Insulation Type, channel
to system
Type tested at 3250V DC for 60 s

North American temp code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication

1770-4.1

.

(2)

RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Input Specifications – 2005-IA8 and 2085-IM8

Attribute

2085-IA8

2085-IM8

Number of Inputs

8

Voltage category

120V AC

240V AC

Operating voltage range

74…120V AC

159…240V AC

Off-state voltage, max

20V AC

40V AC

Off-state current, max

2.5 mA

On-state current, min

5.0 mA @ 74V AC

4.0 mA @ 159V AC

On-state current, max

12.5 mA @ 120V AC

7.0 mA @ 240V AC

Input impedance, max

22.2 k

Ω

Inrush current, max

450 mA

Input filter time
Off to On
On to Off

20 ms

IEC type compliance

Type 3

Output Specifications - 2085-OA8

Attribute

Value

Number of Outputs

8

Voltage category

120V/230V AC

Operating voltage range

120…240V AC

Output voltage, min

85V AC

Output voltage, max

240V AC

Off-state current, max

2.5 mA

On-state current, min

10 mA per output

On-state current, max

0.5 A per output

On-state current,
per module, max

4 A

General Specifications

Attribute

2085-IA8

2085-IM8

2085-OA8