Ground your kinetix 350 drive to the subpanel – Rockwell Automation 2097-Vxxx Kinetix 350 Single-axis EtherNet/IP Servo Drive Installation Instruction User Manual
Page 13

Kinetix 350 Single-axis EtherNet/IP Servo Drives 13
Rockwell Automation Publication 2097-IN008D-EN-P - July 2013
Ground Your Kinetix 350 Drive to the Subpanel
If the Kinetix 350 drive is mounted on a painted subpanel, ground to a bonded cabinet ground
bus with a braided ground strap or 4.0 mm
2
(12 AWG) solid-copper wire, 100 mm (3.9 in.) long.
Connecting the Braided Ground Strap
For dimensions, see
Kinetix 350 Drive Mounting Dimensions
on
page 6
.
ATTENTION: To avoid personal injury and equipment damage, verify the following:
•
Installation complies with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline
provisions for safely installing electrical equipment.
•
Motor power connectors are used only for connection purposes. Do not use motor power
connectors to turn the unit on and off.
•
Shielded power cables are grounded to prevent potentially high voltages on the shield.
Bonded Cabinet
Ground Bus
Ground Grid or Power
Distribution Ground
Braided
Ground Strap
Ground Stud