Rockwell Automation 5000 Intrinsically Safe Version User Manual

Photoswitch, Division 1 installation wiring diagrams

Advertising
background image

Allen-Bradley Control Drawing #133-451 (Ver 08)

PHOTOSWITCH

®

Photoelectric Sensors Series 5000 Intrinsically Safe Version

Division 1 Installation Wiring Diagrams

10mA Max.

Load

Supply Return

Signal

Return

Power Supply

( + )

( -- )

Out

Gnd

Earth Ground

(less than 1 ohm)

In

Gnd

Barrier Bus

Gnd

AB #897H-S140

Out

AB #897H-S120

Gnd

In

Barrier Entity Parameters

—

Load Supply

Power Supply

Load

Supply Return

( + )

( + )

Out

Gnd

Earth Ground

(less than 1 ohm)

Gnd

In

In

Gnd

In

Gnd

Out

Load

Supply

( +5V DC)

Earth Ground

(less than 1 ohm)

Out

AB #897H-S120

Gnd

In

In

Gnd

Gnd

Out

Barrier Entity Parameters

—

Power Supply

42DRA--5500, 42DRU--5500
42DRP--5500, 42DRU--5700

42DTB--5500

NPN Open Collector Connections (Sinking)

(2 Barriers Required)

Class I, II, III, Division 1, Group C, D, E, F, G
Class I, II, III, Division 2, Group A, B, C, D, F, G

Zener Diode Barriers

Power Supply

& Load Circuits

Nonhazardous Location

Hazardous Location

Photoheads

Terminal Base

Vmax = 29.5V

Imax = 107mA

AB #897H-S120

Gnd

Load

TTL

Device

Supply Return

( + )

( + )

( + )

( -- )

PNP Open Collector Connections (Sourcing)

(3 Barriers Required)

Vmax = 29.5V

Imax = 107mA

Terminal Base

Photohead

Sink Wiring

Terminal Base

Photohead

Source Wiring

( + )

( 1 )

( -- )

( + )

( 2 )

( 3 )

( -- )

Barrier Bus

AB #897H-S120

Out

Barrier Entity Parameters

—

AB #897H-S120

Gnd

Barrier Bus

Gnd

AB #897H-S140

( -- )

Signal

Return

Class I, II, III, Division 1, Group A, B, C, D, E, F, G
Class I, II, III, Division 2, Group A, B, C, D, F, G

PNP Open Collector Connections (Sourcing)

(2 Barriers Required)

Vmax = 29.5V

Imax = 107mA

Terminal Base

Photohead

Source Wiring

( + )

( 2 )

( 3 )

( -- )

Notes:
– Installation must be in accordance with the National Electrical Code

®

(NFPA 70, Article 504), ANSI/ISA--RP12.6, and the manufacturer’s instructions.

— Barrier entity parameters: Voc 29.5V; Isc 107mA; Ca Ccable; La Lcable; recommended barriers are indicated on the above wiring diagram.

˜ If the electrical parameters of the cable used are unknown, the following values may be used: Capacitance -- 60pF/ft.; IInductance -- 0.20 H/ft.

™ Barrier bus must be insulated from other grounded metal. Use DIN Rail Mounting Kit, Allen-Bradley #64--136.

š Maximum nonhazardous area voltage must not exceed 250V.

› Barriers are not required for Division 2 (29.5V DC max.). Division 2 applications must be installed in accordance with the National Electrical Code

®

.

œ An approved dust tight seal is required for Class II, III applications.

 The output circuits of Zener Diode Barriers shall be in separate cables or separated from each other per NEC 504--30.

ž No revision to drawing without prior FMRC and UL approval.

Ci = 0 F
Li = 0 H

µ

µ

Ci = 0 F
Li = 0 H

µ

µ

Ci = 0 F
Li = 0 H

µ

µ

24V DC 8%

±

24V DC 8%

±

24V DC 8%

±

<

<

>

>

µ