About the pullup board, Install the pullup board – Rockwell Automation 2711P-RPPU PanelViewPlus Logic Module Pullup Board User Manual
Page 3
 
PanelView Plus and VersaView CE Logic Module Pullup Board 3
Publication 2711P-IN028A-EN-P - December 2005
About the Pullup Board
The PanelView Plus/VersaView CE Logic Module Pullup Board corrects intermittent 
terminal resets (reboot or power cycle) that have typical reset cycle rates of 
approximately 60 seconds. In addition, a 50 second lock-up is typically observed 
during ‘Invoking Test Monitor’ terminal boot screen.
Affected product Series/Revisions and Date Codes are:
Install the Pullup Board
Product
Catalog Numbers
Series and Revisions
Data Code
PanelView 
Plus/VersaView CE 
Terminals
2711P-x7, 2711P-x10, 
2711-x12, 2711P-x15, 
6182H-x7, 6182H-x10, 
6182H-x12, 6182H-x15
Series A, Revisions A to D
0203 thru 0705 
(Manufacturing dates 
February 2003 to 
July 2005)
PanelView 
Plus/VersaView CE Logic 
Modules
2711P-RP, 2711P-RP1, 
2711P-RP2, 6189-RP, 
6189-RPRH, 6189-RPEH
Series A, Revision A through 
Series C, Revision A
0203 thru 0705 
(Manufacturing dates 
February 2003 to 
July 2005)
WARNING
If you connect or disconnect any communication cable with 
power applied to this module or any device on the network, an 
electrical arc can occur. This could cause an explosion in 
hazardous location installations. Be sure that power is removed or 
the area is nonhazardous before proceeding.
Logic Module Series and 
Revision
Terminal Series and 
Revision
Date Codes