Publication 2711P-IN017A-MU-P

Installation Instructions

Communication Modules

for PanelView Plus 400 and 600 Terminals

Catalog Number 2711P-RNxxx

English

You can attach a Communication Module to the base configured unit of a
PanelView Plus 400/600 terminal with a network interface. These modules are
available as separate catalog numbers for field installation. The installation is the
same for all modules regardless of the communication protocol.

To install a communication module:

1. Disconnect power from the terminal.

2. If Display Module is removed from panel, set the module, display side

down, on a clean, flat, stable surface to prevent scratches.

3. Remove the label covering the connectors on the base unit of the terminal.

ATTENTION

!

If you connect or disconnect any communication cable with
power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.

REMOVE LABEL TO INSTALL
COMMUNICATION MODULE