Rockwell Automation 2100 Install Ground Strap-Bul.2100/2400 Unit Door User Manual
Centerline
 
2100-5.37 - July 1999
CENTERLINE
®
Motor Control Centers
Install Door Ground Strap on Bulletin 
2100/2400 Unit Door
Instructions
Application
Use these instructions to install a door ground strap (2100H-GD1) on all 
Bulletin 2100 motor control center unit doors.
Recommended Tools
Adjustable wrench or 3/8” socket
Drill
.203 bit
Installation
Refer to Figure 1 and use the following steps to install door ground strap:
1. Make sure that all power has been disconnected.
2. Verify parts list (see Figure 1).
3. Modify door according to dimensions in Figure 2.
A. If door mounted equipment interferes with the location of the hole
modification, hole can be moved slightly.
B. If door mounted equipment interferes with mounting the ground
 strap onto the bottom hinge, the ground strap can be mounted on 
 the next available hinge.
C. If door mounted equipment does not allow the ground strap to fit
 between the hole and the hinge, the hole modification location may 
 be moved significantly so that the ground strap can reach a door 
 hinge.
4. To install door ground strap:
A. Remove bolt on the hinge being used.
B. Install ground strap onto hinge as shown in Figure 1. Torque 1/4-20
hinge bolt to 65 lb-in (7.1 N-m).
C. Install ground strap to door as shown in Figure 1. Torque #10-32
carriage bolt to 40 lb-in (4.3 N-m).
!
ATTENTION: De-energize all power sources to the motor 
control center before installing door ground strap. Failure to 
de-energize all power sources can result in severe injury or 
death.