Module spacing, Din rail mounting – Rockwell Automation 2080-LC50-24AWB_24QBB_24QVB_24QWB Micro850 24-Point Programmable Controllers Installation Instructions User Manual

Page 9

Advertising
background image

Micro850 24 Point Programmable Controllers 9

Publication 2080-IN007B-EN-P - April 2014

Mounting Dimensions and DIN Rail Mounting

Module Spacing

Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2.0 in.) of space on all sides for adequate ventilation. If optional accessories/modules
are attached such as the power supply 2080-PS120-240VAC or expansion I/O modules, make
sure that there is 50.8 mm (2 in.) of space on all sides after attaching the optional parts.

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 mm x 1 mm
(EN 50 022 - 35 x 7.5).

Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and
pry it downwards until it is in the unlatched position.

1. Hook the top of the DIN rail mounting area of the controller onto the DIN rail, and

then press the bottom until the controller snaps onto the DIN rail.

2. Push the DIN rail latch back into the latched position.

Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAHJ35)
for vibration or shock environments.

TIP

For environments with greater vibration and shock concerns, use the panel
mounting method, instead of DIN rail mounting.

45912

Mounting dimensions do not include mounting feet or DIN rail latches.

158 mm (6.22 in.)

80 mm (3.15 in.)

90 mm
(3.54 in.)