Installing a Control Power Fuse
Use this procedure to install the fuse:
1. Verify that the fuse is of the correct size and type:
2. Use the fuse-puller to press the fuse into place.
Note: Rejection type fuses can only be installed one way.
3. Replace any Lexan guards that you removed.
4. Dispose of the removed part according to your company’s procedures
and local ordinances.
Bulletin 2364 Current Code
Control Power Fuse
A
2A, KLDR
B
2A, KLDR
C
3A, KLDR
D
4A, KLDR
E
5A, KLDR
F
12A, KLDR
G
12A, KLDR
J
3.5A, KLDR
K
5A, KLDR
L
6.25A, KLDR
M
12A, KLDR
N
15A, KLDR (F7)
10A, KLDR (F5)