Wiring options for the 2085-iq32t module – Rockwell Automation 2085-IQ16_IQ32T 24V DC 16 and 32 Sink/Source Input Modules User Manual
Page 10
 
10 Micro800 16-point and 32-point 12/24V Sink/Source Input Modules
Publication 2085-IN001A-EN-P - September 2012
Wiring Options for the 2085-IQ32T Module
Included with your 2085-IQ32T module is a keyed 40-pin female connector and crimp type 
pins. These components allow you to wire I/O devices to the module using a 40-conductor cable 
or individual wires. 
When assembled, align the female connector over the module’s male header using the keying slot 
as a guide. Firmly lock them together with the upper and lower retaining arms.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected I/O must be 
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
WARNING: Do not unlatch the connector retaining arms or remove the connector while power 
is on. This could cause an explosion in hazardous location installations. Be sure that power is 
removed before proceeding.
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source 
compliant with the following:
Class 2 or Limited Voltage/Current.
I-00
I-01
I-02
I-03
I-04
I-05
I-06
I-07
I-08
I-09
I-10
I-11
I-12
I-13
I-14
I-15
COM0
COM0
COM1
COM1
I-16
I-17
I-18
I-19
I-20
I-21
I-22
I-23
I-24
I-25
I-26
I-27
I-28
I-29
I-30
I-31
COM2
COM2
COM3
COM3
45300
2085-IQ32T