Hazardous location approval – Rockwell Automation 1798-OB8E FlexArmor 24V dc Sourcing Output Modules User Manual

Page 7

Advertising
background image

FlexArmor 24V dc Sourcing Output Modules 7

Publication 1798-IN002A-EN-P - January 2001

Hazardous Location Approval

The following information applies only to products marked
with Hazardous Location Approval, when operating in
hazardous locations:

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with markings
on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the
most adverse temperature code (lowest “T” number) may be used to
help determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time of
installation.

-20°

40°

60°

1A

0.5A

Ambient Temperature (Celsius)

O

u

tpu

t Cur

rent (

per chan

nel)

Derating Curve

42700