4 Kinetix 5500 AC Line Filters

Rockwell Automation Publication 2198-IN003A-EN-P - July 2012

Wire the AC Line Filter

Wire should be copper with 75 °C (167 °F) minimum rating. Phasing of main AC power is
arbitrary and earth ground connection is required for safe and proper operation.

Wiring Examples for the AC Line Filter

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the values and
methods provided.

IMPORTANT

When wiring the line filter for single-phase operation, do not make connections to the L3
terminals. Line and load designations must be observed to meet product specifications.

L1

L2

L3

L1

L2

L3

PE

L1’

L2’

L3’

PE

240/480V

L1

L2

L3

L1

L2

L3

PE

L1’

L2’

L3’

PE

240V

Bonded Cabinet
Ground Bar

2198-DB08-F

AC Line Filter

Input Fusing

Mains AC Input

Line

Load

Bonded Cabinet
Ground Bar

2198-DB

xx-F

AC Line Filter

Input Fusing

Mains AC Input

Kinetix 5500 drive input
power (IPD) connections
for three-phase operation.

Line

Load

Kinetix 5500 drive input
power (IPD) connections
for single-phase operation.